Washington’s Department of Labor & Industries (L&I) released findings on November 20 from the Nippon Dynawave white-liquor tank failure in Longview. According to the agency, the company operated for 43 weeks without correcting a warning that the tank wall was below minimum safe thickness. The tank ruptured on May 26, 2026, killing 11 workers and injuring 12. These are Washington investigation findings, not legal requirements automatically applicable to a Korean mill.

The operational problem

An inspection reading must connect to a decision: repair, modified operating condition, isolation or retirement, followed by documented authorization before service resumes. Without clear ownership and records, a warning may never become an action. This article concerns new safety findings, not the previously discussed Longview production outlook.

Illustrative tank-wall thickness measurement, not the failed tank

Evidence to check

L&I says three reports between August 2025 and February 2026 identified severe corrosion. The agency explains that under API 653, a tank below minimum safe thickness must be repaired, operated at reduced capacity to lower pressure, or retired. Its findings also address inspection of other tanks and emergency response. The release describes agency citations at a stage when the company still has an appeal period.

Practical output

Link equipment ID, measurement location and value, criterion and source, inspector, report recipient, risk decision, immediate operating limit, repair or isolation choice, verification record and restart approver. For a tank below its applicable safe limit, do not authorize continued operation or restart without an appropriate repair, qualified reduction in allowable capacity or pressure, or retirement decision, followed by competent verification. Maintain emergency-plan and training records alongside, but distinct from, mechanical-integrity records.

Illustrative maintenance records beside an isolated tank, not the incident scene

When to hold a conclusion

Do not assume API 653 applies unchanged to every Korean installation. Local law, design, inspection standards and qualified engineering judgment govern each site. A public news release cannot supply a specific tank’s allowable thickness or restart clearance.

About the Author

PackingMaster: PaperPackLog editor covering paper packaging markets, products and technology.

References

Checked November 21, 2026. Washington findings are distinct from local compliance decisions.